3
YESNO
YES
NO
If the error persists, please complete sections 1 and 5 and return to DEVI.
HEATING ISSUE 3
The floor is not
heating up at all.
If the issue is not
resolved, please complete
section 1 and 5 and
return to DEVI. You will be
contacted upon receipt.
Is the outer rim on the
thermostat flashing?
Please ensure that the
thermostat is set to the
quick set up on page 3.
Is the symbol
showing?
HEATING ISSUE 4
The system is heating,
but not performing as
I would expect.
Please refer to the
Performance Trouble
Shooter on page 4.
Please refer to the user
guide/faq’s on
www.devi.co.uk
complete the applicable forms where required
Read the following fault number on the thermostat and follow instructions.
2
Configured as a master, but another master is
detected
Thermostat incorrectly
set during configuration, see step 2,
on page 5 and 6. Set to ALO.
No Error Action
7
Clock is not set Set the clock
(see page 11 of the devireg 550 user guide,
This can be downloaded on www.devi.co.uk).
3
Configured as a slave but cannot find any master
unit
Thermostat incorrectly set during
configuration, see step 2, on page 5 and 6.
Set to ALO.
4
The thermostat has switched itself off, due to
overheating
Call an elecrician, (let the thermostat cool for
a period then enter basic set-up to leave error
mode). Check all wiring, (diagrams on back of
thermostat and on www.devi.co.uk) and the
visual checks on page 4.
5
Sensor fault. Floor sensor short circuit Call an electrician (Have an authorised
electrician check the floor sensor wiring and
obtain a resistance reading of 10K - 24K Ohms).
The floor sensor may have to be re-wired or
replaced.
6
Sensor fault. Floor sensor short circuit Call an electrician (Have an authorised
electrician check the floor sensor wiring and
obtain a resistance reading of 10K - 24K Ohms).
The floor sensor may have to be re-wired or
replaced.