devireg 550 test instructions for the devimat floor warming system or areas
where the thermostat is situated outside of the room (ie. wet areas)
Please follow these instructions to ensure that the thermostat is set-up correctly in order to provide power to the heating elements.
NB. If the thermostat is displaying CODE initially you will ONLY be presented with step 1 and step 4; set these as described below.
Once you have either completed steps 1 and 4, or the controller is displaying something other than CODE, you must press and hold
the button until the word CODE is displayed and follow the steps below. To reset the thermostat, press and hold the button until CODE
is displayed. Please note that the setup for older versions can be seen in RED.
NB. If the thermostat is flashing at any time, please revert to the Trouble Shooter on page 2.
Setup code
1
2
3
4
5
Rotate button to select code 0044 and then press
button once.
Rotate button to select ALO and then press the button
Operating
mode
Rotate button to select ‘FS’ to activate the floor sensor,
then press button. This is a floor sensor only selection.
Sensor
selection
Maximum
floor
temperature
selection
6
LO should be displayed, you should rotate the dial to
select -30ºC then press the button.
Off periods
7
Rotate the button to select clock display as either 24
hours or 12 hours AM/PM.
Clock
display
8
Press button once.
Save
settings
9
Press and hold button. The display now shows the time
and day (number 1 represents Monday, number 7 is
Sunday). Rotate the dial to show the correct time and
day of the week and then press the button to save the
correct time setting.
Setting the
clock
10
Press the button so there is a black circle around the
outside of the digital display. The thermostat is now in
manual mode.
Manual
mode
11
For test purposes, turn the setting up to 10 until
is displayed. This may take a few minutes to
display. This ensures that the thermostat is
sending output to the heating element.
This temperature setting is simply for test purposes.
When it is apparent that the floor is heating, lower the
temperature immediately. This should be evaluated over
a 24 hour period).
Test
temperature
Adaptive
mode
Temperature
readout
Rotate button to select ºC and then press button
Rotate button to select AdAP and then press button
System
Floor construction
Tiles
Timber
Carpet
devimat
Timber base
29-32ºC
27-32ºC
29-32ºC
devimat
Concrete base
40-45ºC
29-32ºC
40-45ºC
At ‘nt’ rotate button to select either of the following
temperature selection, maximum floor temperatures,
then press button.
4