devireg 550 test instructions for the deviheat total heating system
Please follow these instructions to ensure that the thermostat is set-up correctly in order to provide power to the heating
elements. If the thermostat is displaying CODE initially you will ONLY be presented with step 1 and step 4; set these as described
below. Once you have either completed steps 1 and 4, or the controller is displayng something other than CODE, you must press
and hold the button until the word CODE is displayed and follow the steps below. To reset the thermostat, press and hold the
button until CODE is displayed.
Please note that the setup for older versions can be seen in RED.
NB. If the thermostat is flashing at any time, please revert to the Trouble Shooter on page 2.
System
Floor construction
Tiles
Timber
Carpet
Cable
Cable screed
40-45ºC
36ºC
40-45ºC
Cable
Timber suspended
36ºC
36ºC
36ºC
Setup code
1
2
3
4
5
Rotate button to select code 0044 and then press
button once.
Rotate button to select ALO and then press the button
once.
Operating
mode
Rotate button to select ºC and then press button.
Rotate button to select rFS to activate the floor sensor,
then press button. This is a room and floor sensor
selection.
Sensor
selection
Maximum
floor
temperature
selection
7
LO should be displayed, you should rotate the dial to
select -15 degrees C then press the button.
Off periods
6
This should be set to 0.0, if this is the case, press the
button to continue. If not, adjust setting and continue.
OFFS
8
9
Press button once.
Save
settings
10
Press and hold button. The display now shows the time
and day (number 1 represents Monday, number 7 is
Sunday). Rotate the dial to show the correct time and
day of the week and then press the button to save the
correct time setting.
Setting the
clock
11
Press the button. A black circle around the outside of
the digital display should be displayed. The thermostat
is now in manual mode.
Manual
mode
12
For test purposes, turn the temperature up to 35ºC until
is displayed. This may take a few minutes. This
ensures that the thermostat is sending output to
the heating element. This temperature setting is simply
for test purposes. When it is apparent that the floor is
heating, lower temperature immediately. This should be
evaluated over a 24 hour period).
Test
temperature